Operating instructions

A3G630-AD03-A1

Translation of the original operating instructions

CAUTION
Electrical voltage

The fan is a built-in component and features no electrically
isolating switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole separating switch.

→ When working on the fan, you must switch off the

installation/machine in which the fan is installed and secure it
from being switched on again.

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check that the data on the type plate match the connection data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

Protective earth contact resistance as per EN 61800-5-1

Compliance with the resistance specifications as per EN 61800-5-1 for
the protective earth connection circuit must be verified in the application.
Depending on the installation situation, it may be necessary to connect
an additional protective earth conductor by way of the extra protective
earth terminal provided on the device. The protective earth terminal is
located on the housing and provided with a protective earth symbol and
a hole.

4.2.2 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current operated device

If the use of a residual current device (RCD) is required in your
installation, only pulse current-sensitive and/or universal
residual current devices (type A or B) are permissible.
Residual current devices (RCD) cannot provide personal safety
while operating the device, as is also the case with frequency
converters. When the device power supply is switched on,
charging current pulses from the capacitors in the integrated
EMC filter can lead to the instant triggering of residual current

devices. We recommend residual current circuit breakers
(RCCB) with an activation threshold of 300 mA and delayed
tripping (super-resistant, characteristic K).

If the use of a residual current device (RCD) is required in your
installation, only universal residual current devices (type B or
B+) are permissible. Residual current devices (RCD) cannot
provide personal safety while operating the device, as is also
the case with frequency converters. When the device power
supply is switched on, charging current pulses from the
capacitors in the integrated EMC filter can lead to the instant
triggering of residual current devices. We recommend residual
current circuit breakers (RCCB) with an activation threshold of
300 mA and delayed tripping (super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection of the cables

External leads are brought out of device.

;

First connect the "PE" (protective earth) connection.

Connect the lines according to your application. When doing so,
observe chapter 4.5 Connection screen.

4.3.1 Cable routing

No water may penetrate along the cable in the direction of the cable exit.

Fans installed lying flat

Fig. 1: Fan installed lying flat, cable routed as a water trap.

Fans installed in upright position

Item no. 50323-5-9970 · ENG · Revision 89187 · Release 2016-04-14 · Page 7 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G630-AD03-A1

Страница 1: ...device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once...

Страница 2: ...device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impell...

Страница 3: ...device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibration...

Страница 4: ...n of air flow V 2 Depth of screw max 10 mm 3 Connection line PVC AWG18 5 x crimped core end sleeve 4 Connection line PVC AWG22 3x crimped core end sleeves Item no 50323 5 9970 ENG Revision 89187 Relea...

Страница 5: ...finition with optimum efficiency The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 5 8 kg Size 630 mm Surface of rot...

Страница 6: ...be damaged Set down the fan carefully on a soft surface Make sure the blades are not subjected to load After installation make sure the impeller moves easily and that the blades of the impeller are n...

Страница 7: ...witched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If th...

Страница 8: ...th which the device is pre set by ebm papst Operation mode PWM controlling Group adress 01 Fan device adress 01 Max PWM 100 Min PWM 0 Save set value to EEPROM No Set value control Analog Control funct...

Страница 9: ...connection 2 A max 250 VAC min 10 mA 1 6 NC white 2 Floating status message contact normally closed connection 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 kOhm SELV 2 11 10 VDC re...

Страница 10: ...ct the device from the supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to s...

Страница 11: ...sary Visual inspection At least every 6 months Open bore holes Weld seams for crack formation Visual inspection At least every 6 months Replace device Abnormal bearing noise acoustic At least every 6...

Страница 12: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power lines Cables for internal wiring Electrolytic...