Removal Procedure
SiBE811120
46
Photocatalytic Air Purifier L-Series
9.3
Removal of Ionized Wire
Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1
Unfasten the 2 hooks
and lift the opposing
pole plate to detach.
The opposing pole plate has
the same shape in 4
directions.
2
Pinch and detach the
ionized wires with
pincers.
Caution
Be careful not to get your hands
cut by the ionized wires.
Once removed, the ionized
wires cannot be reused.
When cleaning the ionized
wires, do not remove them.
(Refer to the Operation
Manual.)
3
4
Remove the 3 screws
and remove the ionized
wire mounting frame
and contact switch.
Remove the 3 screws
and remove the contact
switch for ionized wire.
Hook
(R12351)
(R12352)
Opposing
pole plate
Ionized wire
(R12353)
(R12354)
Contact switch
Ionized wire
mounting frame
Contact switch
for ionized wire