3
|
Components
Service manual
92
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
d
c
b
a
A
A
ARXP-L + ARXP-M + RXP-L + RXP-M + RXP50~71N units
a
V DC out (+)
b
V AC in
c
V AC in
d
V DC out (–)
d
c
b
a
A
A
ARXP20~35N + RXP20~35N units
a
V DC out (+)
b
V AC in
c
V AC in
d
V DC out (–)
INFORMATION
When measuring on the front of the main PCB, make sure to locally remove the
protective varnish with the test leads of the multi meter.
VDC
Com
Ref
VDC
Com
Ref
d
b
0.51~0.52 V
b
d
O.L
b
a
0.51~0.52 V
a
b
O.L
d
c
0.51~0.52 V
c
d
O.L
c
a
0.51~0.52 V
a
c
O.L
4
If the diode module is NOT OK, replace the main PCB, see
96].