3
|
Components
Service manual
91
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
b
a
A
A
ARXP20~35N + RXP20~35N units
a
+ terminal
b
– terminal
INFORMATION
When measuring on the front of the main PCB, make sure to locally remove the
protective varnish with the test leads of the multi meter.
Is the measured rectifier voltage
correct?
Action
Yes
Perform a check of the power modules,
see
No
Replace the main PCB, see
To perform a diode module check
1
First check the rectifier voltage of the main PCB, see
INFORMATION
If the rectifier voltage is OK, the diode module is OK. If rectifier voltage is NOT OK,
replace the main PCB.
Below procedure describes how to check the diode module itself.
Prerequisite:
Stop the unit operation via the user interface.
2
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
3
Check the diode module in reference with the image and the table below.