To perform a power module check
Prerequisite:
First check the rectifier voltage of the main PCB, see
Prerequisite:
Stop the unit operation via the user interface.
1
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
Power module IPM1 for compressor
1
Disconnect the compressor connector from the main PCB.
2
Check the power module IPM1 in reference with the image and the table
below.
e
d
a
b
c
A
A
ARXP-L + ARXP-M + RXP-L + RXP-M + RXP50~71N units
a
U
b
V
c
W
d
DC+
e
DC–
e
d a b c
A
A
ARXP20~35N + RXP20~35N units