3
|
Components
Service manual
63
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
a
a
Compressor wire terminals cover
12
If applicable, connect the ground wire to the compressor. Install and tighten
the screw to fix the ground wire.
13
Install the following thermistors in their holder:
▪
Suction thermistor
▪
Discharge pipe thermistor
▪
Compressor body thermistor (if applicable)
14
Install the compressor insulation, see
58].
15
Perform a pressure test, see
144].
16
Add
refrigerant
to
the
refrigerant
circuit,
see
148].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.3 Expansion valve
3.3.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the expansion valve
Prerequisite:
Power OFF the unit for 3 minutes. Then turn ON the unit and listen to
the expansion valve assembly. If the expansion valve does NOT make a latching
sound, continue with the electrical check of the expansion valve, see
63].
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
111].
1
Remove the expansion valve insulation (if applicable) and visually check:
Содержание FTXP20-71L