4
|
Third party components
Service manual
144
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
2
Check the continuity of all wires.
3
Replace any damaged or broken wires.
INFORMATION
If applicable, also check the electrical components between the main power supply
terminal and the indoor unit power supply terminal (e.g. intermediate terminal, noise
filter, fuse, …).
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.2 Refrigerant circuit
4.2.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To check if the stop valves are open
Prerequisite:
Remove the required plate work, see
1
Remove the caps.
a
b
a
Liquid stop valve
b
Gas stop valve
2
Check if the stop valves are completely open.
The refrigerant circuit stop valves are
open?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.