Components
Service manual
83
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
To remove a fuse of the indoor unit main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
111].
1
Remove the fuse from the PCB.
a
a
Fuse
2
To install a fuse on the indoor unit PCB, see
To install a fuse on the indoor unit main PCB
1
Install the fuse on the correct location on the PCB.
CAUTION
Make sure the fuse is plugged‑in correctly (contact with the fuse holder).
a
a
Fuse
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
main PCB and continue with the next
procedure.