Components
Service manual
89
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
All LED’s of the inverter analyzer are lit
during inverter test?
Action
Yes
Return to
continue with the next procedure.
No
Replace the main PCB, see
To check the fuse of the main PCB
ARXP-L + ARXP-M + RXP-L + RXP-M + RXP50~71N units
Prerequisite:
First perform all earlier main PCB checks, see
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a
a
Fuse
Blown fuse on the main PCB?
Action
Yes
Replace the blown fuse, see
96].
No
Return to
continue with the next procedure.
ARXP20~35N + RXP20~35N units
Prerequisite:
First perform all earlier main PCB checks, see
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.