
6
|
Technical data
Service manual
189
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
6.7.2 Field settings: Outdoor unit
To set the facility settings
INFORMATION
These settings are only to be used for facilities such as equipment or computer
rooms and never in a residence or office with people.
1
Cut the jumper J6 on the circuit board using nippers or a similar tool to
expand the operation range of the outdoor unit down to –15°C.
INFORMATION
The outdoor unit will stop operating when the temperature drops below –20°C and
start back up once the temperature rises again.
2
Below is an overview of the other jumpers settings:
▪
J5: No function for this unit
▪
J8: Cold region setting (changing the operating range from
–10°C to –15°C)
▪
J9: No function for this unit
▪
J11: Protection for error memory overwrite (only to be used during
development)
▪
J12: No function for this unit
Содержание FTXP20-71L
Страница 190: ......
Страница 191: ......
Страница 192: ...ESIE18 01E 2023 01 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...