Troubleshooting - Outdoor Unit Related
Si18-201
272
Service Diagnosis
3.3.10
Fan Position Detection Error
Outdoor Unit
Indication
H7
Method of
Malfunction
Detection
Fan malfunction is detected by checking 3 numbers motor position detection signal.
Malfunction
Decision
Conditions
When the same state with 3 numbers motor position detection signal was kept for 5 seconds.
"
When a fan malfunction is generated 4 times, the system shuts down.
(The 4-time counter resets itself when no outdoor unit abnormality occurs within 60-minute
cumulative time after the malfunction generation.)
Supposed
Causes
"
Incorrect connectors connection
"
Faulty fan PC board
"
Faulty fan motor
Troubleshooting
Check No.4
Refer to P.301
Turn the power supply off.
YES
Correct the connection.
Temporary causes including
noise, etc. are supposed.
Replace fan motor.
Replace fan PC board.
Is the
malfunction
re-generated when turning the
power supply
on again?
NO
YES
Is the motor position
signal output?
NO
(MF029)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are PC board
connectors and relay
connector correctly
connected?
NO
YES
Check No. 4
Fan motor check
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...