System control
Si18-201
130
Main Functions
3.14
Gas Shortage Malfunction
Outline
A gas shortage malfunction is detected by using electric current and by judging the discharge
pipe temperature and motorized valve opening degree.
Details
Gas shortage detection based on current
The current-based gas shortage detection is conducted when the operating frequency
exceeds 55 Hz. When the following condition is met, a gas shortage malfunction is
determined.
Input current
≤
(23/256) × Operating fre(-3.5) A
Gas shortage detection based on discharge pipe temperature and motorized valve
opening degree
This gas shortage detection method uses either the opening of the motorized valve of the BP
or outdoor unit.
1. Gas shortage detection based on BP motorized valve opening and discharge pipe
temperature
Gas shortage malfunction is determined when the following condition is met during
discharge pipe temperature control.
When discharge pipe temperature (DO) > 1 × target discharge pipe temperature (DOSET) +
20°C, motorized valve MAX flow rate signal from operating BP is continuously received for
80 seconds.
2. Gas shortage detection based on outdoor unit motorized valve opening and
discharge pipe temperature
Gas shortage malfunction is determined when the following condition is met during cooling
mode discharge pipe temperature control.
When discharge pipe temperature (DO) > 1 × target discharge pipe temperature (DOSET) +
20°C, condition (EVG
≥
450 pulses) remains for 80 seconds.
Shortage of refrigerant charge is judged when the following condition are satisfied during
discharge temperature control in heating operation.
At Discharge pipe temp. (DO) > Target discharge tempe20ºC and when the
condition of
EVL > 450 pulse continue 80 seconds.
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...