System control
Si18-201
166
Main Functions
3.37
4-Way Valve Operation
3.37.1 4-Way Valve Operation Security
Purpose of the
Function
This function ensures proper operation of the 4-way valve. (Because the pilot-system drive
method is used, the current from the coil cannot provide fail-proof 4-way valve operation.
Therefore, the difference of pressure before and after the valve is used to ensure proper valve
operation.)
Outline
Because the pilot-system drive method is used, the current from the coil cannot provide fail-
proof 4-way valve operation. Therefore, the use of the difference of pressure before and after
the valve is required. At the time of operation when the 4-way valve switches, the operating
frequency exceeding a specified frequency is output for a predetermined time duration to
ensure differential pressure necessary for the 4-way valve operation.
Details
3.37.2 4-Way Valve Switching
Outline
When the outdoor heat exchanger is used as a condenser (in cooling and defrosting), the 4-way
valve is not supplied with current. When the indoor heat exchanger is used as a condenser, it is
supplied with current. To reduce the switching noise when heating operation stops (ON
→
OFF), the 4-way valve switching after heating operation shutdown is delayed.
Details
The 4-way valve switching delay is 140 seconds for OFF delay.
To reduce power consumption during current flow, a OFF process is conducted when the
heating thermostat OFF time exceeds 60 minutes.
Cooling
Heating
Continuing time of 4-way valve
operation
90sec
90sec
Frequency of 4-way valve operation
62Hz
41Hz
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...