System control
Si18-201
134
Main Functions
3.16.2 Input Current Control II (High Pressure Control)
Outline
Based on the input current and input voltage, the compressor output frequency is regulated to
decrease the compressor capacity in order to prevent abnormal rising of the high pressure.
Note
The peak-cut control is similar to this function, but it cannot effectively detect high pressure
during transitional condition due to the thermistor's tracing performance; therefore, the high
pressure can increase abnormally in some cases. This function droops the compressor when a
transitional condition occurs or the high pressure rises suddenly in order to prevent abnormal
rising of the high pressure.
Therefore, the function start area is set higher that the high pressure setting of the peak-cut
control.
The high pressure saturation temperature is estimated from the power consumption (input
voltage, input current), output frequency and suction pressure, and three zones (reset, no-
change and drooping zones). When the high pressure saturation temperature is in one of the
zone, the output frequency limit is varied depending on the type of the zone.
Details
The high pressure is estimated based on the high pressure estimation function (operating
frequency, input current, suction pressure), and the estimated high pressure is used to obtain
the saturation temperature. When the heat exchanger intermediate temperature enters the
overcooling zone, if the peak-cut control does not function, this function prevents abnormal
rising of the high pressure.
Cooling
Heating
A change of 2 Hz is made when each zone fluctuates.
The reset zone is set for 30 sec when compressor operation is started, for 30 sec when the
number of operating room units increase, and for 2 sec when the number of operating room
units decrease.
With each operation of the HPS operation counter, the zone judgement temperature is
decreased by 2°C.
Drooping speed : 2Hz/40sec
Reset zone
No-change zone
Drooping zone
58˚C
60˚C
62˚C
Target temperature
of liquid pipe
temperature rise
in cooling SC
control : 60˚C
(M1023)
Drooping speed : 2Hz/40sec
Reset zone
No-change zone
Drooping zone
56˚C
58˚C
60˚C
(M1024)
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...