Si18-201
System control
Main Functions
155
3.29
Gas Pipe Isothermal Control in Cooling Operation
Purpose of the
Function
This function ensures appropriate refrigerant distribution when many room units are operating in
the cooling mode.
Outline
The gas pipe temperatures of operating room units are detected by the gas pipe thermistors,
and the motorized valves' flow rates are corrected so as to equalize the temperatures of the gas
pipes.
When gas pipe temperature is higher than average
→
Opens the valve of that room unit
When gas pipe temperature is lower than average
→
Closes the valve of that room unit
However, the closing operation is restricted to prevent the valve operation that results in a flow
rate that exceeds a certain level at one time.
(Protection function to prevent rotor frosting)
Details
The gas pipe temperature is detected at every sampling (40 SEC) operation of the gas pipe
isothermal control, and average value DGAV of each gas pipe temperature is obtained.
In order to prevent dew condensation in the connection pipe, when DGAV < Gas pipe lower limit
temp., DGAV = Gas pipe lower limit temp.
Gas pipe lower limit temp. = 0.2 × DOA + 1
0
2
4
6
8
10
12
-20
0
20
40
60
Outside air temperature
Gas pipe lower-limit temperature
(M1048)
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...