Troubleshooting - Outdoor Unit Related
Si18-201
266
Service Diagnosis
3.3.4
Operation Halt Due to Detection of INV Input Current Error
Outdoor Unit
Indication
E8
Method of
Malfunction
Detection
INV input current error is detected using INV input current detected by CT.
Malfunction
Decision
Conditions
When the inverter input current of 28A or more continued for 2.5 seconds.
"
When an INV input current error is generated 4 times, the system shuts down.
(The 4-time counter resets itself when no outdoor unit abnormality occurs within 60-minute
cumulative time after the error generation.)
Supposed
Causes
"
Faulty wiring connection of filter PC board and control PC board
"
Faulty compressor
"
Overcurrent due to faulty PC board
"
Incorrect detection due to faulty PC board
"
Short-circuit
Troubleshooting
Check No.5
Refer to P.302
Check No.6
Refer to P.303
Check No.7
Refer to P.304
Check No.1
Refer to P.300
Check No.2
Refer to P.300
YES
Apply required remedy
subject to the case.
Replace control PC board /
filter PC board.
Apply required remedy
subject to the case.
Apply required remedy
subject to the case.
Apply required remedy
subject to the case.
(MF023)
Check No. 1
Installation conditions check
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Does the
INV input current
(integrated input indoor
current) as shown
left flow?
NO
Check No. 5
Wiring connection check to
run.
Make sure of integrated input
current (Substitution of INV
input that can not be measured)
Check No. 6
Power transistor check
Check No. 7
Power transistor output check
OK
Check No. 2
Discharge pressure check
(Note* Indoor current=0-4.5A)
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...