Si18-201
Troubleshooting - Outdoor Unit Related
Service Diagnosis
287
3.3.24
Electronic Thermal
Outdoor Unit
Indication
L8
Method of
Malfunction
Detection
Electronic thermal is detected using output amperage and operating status.
Malfunction
Decision
Conditions
When the compressor output current of 40A or higher continued for 260 seconds
When the compressor output current of 50A or higher continued for 5 seconds
"
When an electronic thermal error is generated 4 times, the system shuts down.
(The 4-time counter resets itself when no outdoor unit abnormality occurs for 60-minute
cumulative time after the error generation.)
Supposed
Causes
"
Incorrect connectors connection
"
Faulty thermistor
"
Faulty power transistor
"
Disconnection·Faulty connection of internal wiring
"
Faulty reactor
"
Faulty compressor
"
Faulty PC board
Troubleshooting
Check No.5
Refer to P.302
Check No.6
Refer to P.303
Check No.7
Refer to P.304
Check No.1
Refer to P.300
Check No.2
Refer to P.300
Check No. 5
Main circuit wiring
connection check
NO
Replace control PC board.
Apply required remedy
subject to the case.
Apply required remedy
subject to the case.
Apply required remedy
subject to the case.
When halting,
does the current stated
above?
(MF043)
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check output current
(Measure motor current of
U,V,W with use of clamp meter.)
Check No. 6
Power transistor check
Check No. 7
Power transistor output check
OK
Check No. 1
Installation conditions check
OK
Check No. 2
Discharge pressure check
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...