Si18-201
Troubleshooting - Outdoor Unit Related
Service Diagnosis
295
3.3.31
Operation Halt Due to Detection of Gas Shortage
Outdoor Unit
Indication
U0
Method of
Malfunction
Detection
Detection Method 1
Lack of gas is detected using the input current detected by the CT and the compressor's
operating frequency.
Detection Method 2
Lack of gas is detected using the discharge pipe temperature and the motorized valve opening.
Malfunction
Decision
Conditions
Detection Method 1
Input current < 0.09 × Compressor's operating frequency -3.5
However, when the above state continued for 7 minutes with the operating frequency > 55(Hz)
Detection Method 2
discharge pipe temperature >Target discharge pipe tempe20°C, that should be
continued for 80 seconds or longer with motorized valve full opening.
Note:
The target discharge pipe temperature is calculated with the microcomputer.
Supposed
Causes
"
Gas shortage due to refrigerant leak
"
Faulty gas shortage sensor
"
Input current drop due to faulty compression of the compressor
∗
Disconnection of thermistor (all thermistors)
∗
Faulty CT
"
Faulty, Disconnected motorized valve
"
Incorrect wiring, piping
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...