System control
Si18-201
148
Main Functions
3.26.3 Outdoor Unit Motorized Valve Control in Startup and During the
Number of Operating Room Units Change
Outline
This function improves the convergibility of refrigerating cycle during startup (operation
startup, when the number of operating room unit changes, in thermostat reset).
It also ensures sufficient oil level for compressor startup (low-temperature heating operation
start).
The adverse effects caused by the motorized valve opening to the operation control in startup
are as follows.
When the motorized valve opening is more than the appropriate degree;
Poor control of refrigerant flowing noise (due to lack of subcooling, the convergibility is
insufficient)
(HP does not increase, LP does not decrease
→
no warm/cool air).
Prolonged wet operation (presently no standard set for wet operation).
When the motorized valve opening is less than the appropriate degree;
Prolonged pull-down (increase of compressor internal temperature).
Reduced oil return (low oil level).
Rotor due condensation during cooling.
Details
Initial opening of outdoor unit motorized valve.
Initial opening of outdoor unit motorized valve during cooling operation is according to the
followings:
KBP = FPIMN / initial frequency
"
In case of FPIMN / initial frequency < 1.2
When initial frequency is larger than FPIMN/1.2 = 0.83
EVL = 0
EVG = 50
EVP = 0
"
In case of 1.2
≤
FPIMN / initial frequency
When initial frequency is equal or smaller than FPIMN/1.2 = 0.83
EVL = 52
EVG = 90
EVP = 330 × KBP - 346
Initial opening of outdoor unit motorized valve during heating operation is according to the
followings:
KBP = FPIMN/initial frequency
"
In case of FPIMN / initial frequency < 1
When initial frequency is larger than FPIMN,
EVL = 52
EVG = 60
EVP = 0
"
In case of 1
≤
FPIMN / initial frequency < 1.5
When initial frequency is between 0.67 (= FPIMN/1.5) and 1,
EVL = 52
EVG = 260 × KBP + 60
EVP = 0
Содержание FTX25JVEA9
Страница 9: ...Si18 201 viii Table of Contents...
Страница 71: ...Specifications Si18 201 58 Specifications...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC...
Страница 214: ...Si18 201 Remote Controller Operations 201...
Страница 216: ...Si18 201 Remote Controller Operations 203...
Страница 217: ...Remote Controller Si18 201 204 Operations...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C...