IM 1234-1 • BACNET THERMOSTAT 42 www.DaikinApplied.com
a
pplICaTIon
d
rawIngs
Roof Top Unit – Cooling and Heating with Modulating Valves with Economizer
• Fan status switch (FST) is optional. Typically it is used
only when the BACnet Thermostat is connected to a
network.
• Discharge air temperature (DAT) and outdoor air
temperature (OAT) sensors are required for economizer
operation.
• The remote temperature sensor (RS) is optional.
• Connect the fan output to a 24 volt AC pilot duty input.
• For additional details on connecting sensors, see
Connecting Inputs on page 7
.
• For additional details on connecting the fan and valves,
see
Connecting Outputs on page 8
.
Figure 26: Roof Top Unit Wiring Details—Cooling and Heating with Modulating Valves with Economizer