www.DaikinApplied.com 15
IM 1234-1 • BACNET THERMOSTAT
Setting the Commissioning Setpoints
The commissioning setpoints set the operational setpoints
and limits for the BACnet Thermostat. Setting commissioning
setpoints requires entering Password 2.
NOTE:
Not all setpoints in the following procedure are
applicable to all models of BACnet Thermostat.
Those setpoints are marked as (optional).
Table 7: Setting the Commissioning Setpoints
Procedure
Steps
Display
Starting display
1. Start at the temperature display.
2. Enter Password 2. The display changes to the
MAIN menu display.
Choose and set the setpoints
1. From the MAIN menu, press either the
▲
or
▼
button to select SETPOINT.
2. Press Enter. The SETPOINT menu opens.
3. Choose and set each of the following setpoints.
•
OCC COOL
– The cooling setpoint that is
used as the active setpoint when the system is
occupied
•
OCC HEAT
– The heating setpoint that is used as
the active setpoint when the system is occupied
•
UNOCC COOL
– The cooling setpoint that is
used as the active setpoint when the system is
unoccupied
•
UNOCC HEAT
– The heating setpoint that is
used as the active setpoint when the system is
unoccupied
•
MIN COOLING
– The minimum cooling setpoint
that a user can select as the active setpoint
•
MAX HEATING
– The maximum heating setpoint
that a user can select as the active setpoint
•
DIFFERENTIAL
– The minimum value between
the cooling or heating setpoints. The BACnet
Thermostat will always maintain this difference
between setpoints