IM 1234-1 • BACNET THERMOSTAT
Procedure
Steps
Display
Change the override setpoint
Entering an override setpoint can only take place if the
BACnet Thermostat is in the unoccupied mode.
1. Push the button under unoccupied icon .
NOTE:
If a user password has previously been set up with
a user password, entering a password is not required.
2. Press either the
▲
or
▼
button to change the first digit of
the password.
3. Press the Enter button to select the next digit of the
password.
4. Press either the
▲
or
▼
button to turn the override ON or
OFF.
•
Override Off
– The controller uses the unoccupied
setpoint as the active setpoint
•
Override On
– The controller changes to the occupied
setpoint which can then be temporarily changed
5. Press the Enter button to save the setting.
NOTE:
When the system is in the unoccupied mode,
changing the active setpoint will automatically place the
system in the override mode.
Change the display units
To temporarily change the display units to either Celsius
or Fahrenheit, press and hold the middle button under the
display until the units change.