IM 1234-1 • BACNET THERMOSTAT 26 www.DaikinApplied.com
p
rogram
s
eT
u
p
Procedure
Steps
Display
Calibrate the inputs
Choose CALIBRATION from the ADVANCED menu to
calibrate an input. The BACnet Thermostat includes two
calibration entries; one for the internal temperature sensor
and one for the optional remote temperature sensor
connected to the RS terminal.
Enter a calibration factor to adjust either input for sensor
inaccuracies.
• For a low input reading enter a positive correction value
• For a high input reading enter a negative correction value
Set the display blanking
Choose DISPLAY from the ADVANCED menu to set the
display appearance after the last button is pushed.
•
BLANKING
– Choose one of the blanking options
—
CLOCK
– An analog clock replaces the temperature
and mode icons
—
BACKLIGHT OFF
– The display brightness changes
to the level set by DIM LEVEL after the last button
interaction
—
NONE
– The temperature and mode icons always
remain visible
•
DIM LEVEL
– Sets the level of brightness of the display
back light if BACKLIGHT OFF is the selected blanking
option
Lockout user buttons
Choose KEY LOCKOUT from the ADVANCED menu to limit
the accessibility to users with only Password 1, the user
password.
•
MODE/SETPOINT
– Users with Password 1 cannot
change any value or mode
•
MODE
– Users with Password 1 cannot change the
heating/cooling, fan, or occupancy modes
•
NONE
– Users with Password 1 have full access to
active setpoints, heating/cooling, fan, and occupancy
modes