IM 1234-1 • BACNET THERMOSTAT
Fan Coil Unit – Four-Pipe with Modulating Fan and ON/OFF Valves
• Fan status switch (FST) and discharge air temperature
sensor (DAT) are optional. They are typically used only
when the BACnet Thermostat is connected to a network.
• The remote temperature sensor (RS) is optional.
• Valves are 24 Volt DC.
• Fan starting input is 24 volt AC pilot duty.
• Fan speed input is 0-10 volts DC.
• For additional details on connecting sensors, see
Connecting Inputs on page 7
.
• For additional details on connecting the fan and valves,
see
Connecting Outputs on page 8
.
Figure 17: Fan Coil Unit Wiring Details—Four-Pipe with Modulating Fan and ON/OFF Valves