IM 1234-1 • BACNET THERMOSTAT 40 www.DaikinApplied.com
a
pplICaTIon
d
rawIngs
Rooftop Unit – Two-Stage Gas Heat and Two-Stage DX Cooling with Economizer
• Fan status switch (FST) is optional. Typically it is used
only when the BACnet Thermostat is connected to a
network.
• Discharge air temperature (DAT) and outdoor air
temperature (OAT) sensors are required for economizer
operation.
• The remote temperature sensor (RS) is optional.
• For single stage heating do not connect W2.
• For single stage cooling do not connect Y2.
• Connect outputs to 24 volt AC pilot duty inputs.
• For additional details on connecting sensors, see
Connecting Inputs on page 7
.
• For additional details on connecting the fan and valves,
see
Connecting Outputs on page 8
.
Figure 24: Rooftop Unit Wiring Details—Two-Stage Gas Heat and Two-Stage DX Cooling with Economizer