s
peCIfICaTIons
www.DaikinApplied.com
5
IM 1234-1 • BACNET THERMOSTAT
Environmental Limits
Operating
32 to 120°F (0 to 49°C)
Shipping
-40 to 140°F (-40 to 60°C)
Humidity
0-95% relative humidity (non-condensing)
Installation
Supply Voltage
24 volts AC (-15%, +20%), 50-60 Hz, 12 VA, Class 2 only,
non-supervised. All circuits, including supply voltage, are
power limited circuits.
Weight
Approx 6 ounces (170 grams)
Case Material
Flame retardant plastic
Dimensions
Figure 1: BACnet Thermostat Dimensions
Table 1: BACnet Thermostat Dimensions
A
B
C
3.50 in (89 mm)
5.12 in (130 mm)
1.12 in (29 mm)
BACnet Thermostat Product
Numbers
Description
Product Number
Model Number
Fan Coil Unit
2-pipe and 4-pipe
Modulating or ON/OFF valves
Modulating or Three-Speed Fan
2508035
MIT-FA-005
Roof Top Unit
Modulating or ON/OFF valves
One or two-stages heat
One or two stages cooling
Fan control
Economizer
2508034
MIT-RA-007
Heat Pump Unit
3 heat, 2 cool
Fan Control
Economizer
2508036
MIT-HA-009
BACnet Thermostat Model Nomenclature
MIT F A 0 0 6
MicroTech Integrated Thermostat
Unit Type
F = Fan Coil
R = Rooftop
H = Heat Pump
Vintage
Application
Humidity Sensor
1 = Humidity Sensor
0 = No Humidity Sensor
Motion Sensor
1 = Motion Sensor