Connecting Inputs
The inputs for the BACnet Thermostat are configured for
specific functions and do not require set up in the field. Not all
inputs are required for every application.
Remote Space Temperature Sensor
(optional)
Connect a 10kΩ, Type II thermistor temperature sensor to
the remote space temperature (RS) input and ground (GND)
terminals. The input includes the internal pull-up resistor.
Follow the instructions supplied with the sensor for installation.
When a remote space temperature input is connected to the
BACnet Thermostat, the remote temperature is used instead of
the internal temperature sensor.
Figure 4: Wiring for Remote Space Temperature Sensor
Discharge Air Temperature
Connect a 10kΩ, Type III thermistor temperature probe to the
discharge air temperature (DAT) input. The input includes the
internal pull-up resistor. Follow the instructions supplied with
the sensor for installation.
Figure 5: Wiring for Discharge Air Temperature Sensor
Fan Status Switch (optional)
Connect a Normally Closed Fan Status switch to the Discharge
Air Temperature (DAT) input and ground (GND) terminals.
The input includes the internal pull-up resistor. Follow the
instructions supplied with the switch for installation.
Figure 6: Wiring for a Fan Status Switch
Water Temperature Sensor
Connect a 10kΩ, Type III thermistor temperature probe to the
water temperature (WST) input. The input includes the internal
pull-up resistor. Follow the instructions supplied with the sensor
for installation.
NOTE:
The water temperature sensor is a required input
sensor for 2-pipe fan coil units.
Figure 7: Wiring for a Water Temperature Sensor
Outside Air Temperature
Connect a 10kΩ, Type III thermistor temperature probe to the
outside air temperature (OAT) input. The input includes the
internal pull-up resistor. Follow the instructions supplied with
the sensor for installation.
Figure 8: Wiring for an Outside Air Temperature Sensor