Commissioning Functions
The topics in this section are advanced topics for control
technicians and engineers. These topics cover procedures for
the initial BACnet Thermostat setup.
The BACnet Thermostat commissioning functions are
values and settings that are entered during the installation
and commissioning of a controller and the equipment it is
controlling. Typically these functions do not change after the
installation and commissioning process.
To set up the commissioning functions, you will need the
following information.
• Information about the equipment
• The sequence of operation for the equipment
• The building automation plans for controllers that are part
of a network
Users may change the occupied heating and cooling setpoints
without accessing the commissioning functions.
NOTE:
The instructions for the BACnet Thermostat
commissioning functions cover all of the functions
that can be set in the controller. Not all functions are
available on every model of controller.
Enter the Commissioning Mode
For access to the commissioning functions you will need to
know Password 2.
• If the controller has not been previously set up, no
password is required
• A new Password 2 can be entered in the advanced
commissioning functions
Table 6: Enter the Commissioning Mode
Procedure
Steps
Display
Starting display
Start from the temperature display
Enter the commissioning password
1. Press the left and right buttons below the display at the
same time and hold them until the display changes to the
SECURITY USER LEVEL display.
NOTE:
If Password 2 has not previously been entered, the
display will change to the MAIN menu.
2. Press either the
▲
or
▼
button to change the first digit of
Password 2.
3. Press the Enter button to select the next digit. Repeat for
all four digits. The Enter button is the middle of the three
buttons below the display.