IM 1234-1 • BACNET THERMOSTAT 44 www.DaikinApplied.com
a
pplICaTIon
d
rawIngs
Heat Pump Unit – Three Heat, Two Cool and Economizer
• Fan status switch (FST) and discharge air temperature
sensor (DAT) are optional. They are typically used only
when the BACnet Thermostat is connected to a network.
• The outdoor air temperature sensor (OAT) is required for
compressor lockout based on outside air temperature.
• The remote temperature sensor (RS) is optional.
• For single compressor installations do not connect Y2.
• If auxiliary heat is not required, do not connect AUX/E.
• Connect outputs only to 24 volt AC pilot duty inputs.
• Economizer (ECON) input is 0-10 volts DC.
• For additional details on connecting sensors, see
Connecting Inputs on page 7
.
Figure 28: Heat Pump Unit Wiring Details—Three Heat, Two Cool and Economizer