IM 1234-1 • BACNET THERMOSTAT
Fan Coil Unit – Two-Pipe with Three-Speed Fan and ON/OFF Valves
• The water temperature sensor (WST) is required for two-
pipe units.
• Fan status switch (FST) and discharge air temperature
sensor (DAT) are optional. They are typically used only
when the BACnet Thermostat is connected to a network.
• The remote temperature sensor (RS) is optional.
• The valve is 24 volt AC.
• Fan outputs are for 24 volt AC pilot duty inputs.
• For additional details on connecting sensors, see
Connecting Inputs on page 7
.
• For additional details on connecting the fan and valves,
see
Connecting Outputs on page 8
.
Figure 19: Fan Coil Unit Wiring Details—Two-Pipe with Three-Speed Fan and ON/OFF Valves