74
EXPERT 64EU rev.03
EXPERT 64EU
10.2 Setting the RH Compensation Parameters
Select
9. Advanced Settings
3. Rel. Humidity Compensation*
* This menu is only available if the humidity probe
is activated and if at least 1 RH compensation
function has been enabled (s. 4.4).
• Set the appropriate parameters
amongst the following:
Refer to section 10.1 to get more information on
these parameters.
Minimum Ventilation Compensation:
The following parameters are only accessible if the “
RH in-
fluence on Min.Vent
” function has been activated in the in-
stallation setup (s.4.4). Refer to s.10.1.1 for further infor-
mation on this function.
RH Set Point:
Humidity level above which the minimum ventilation compensation starts. Adjust-
able from 20 to 99% of humidity or to select “Off” to deactivate this function.
Add Min Vent sec:
Speed added to the variable fans in minimum ventilation. Adjustable from 1 to
100%. Select “Off” to deactivate this function.
Stop RH Comp Under:
Select the room temperature below which the minimum ventilation compensa-
tion stops.
Heater Compensation:
The following parameters are only accessible if RH compensation with heating outputs has been activated in the instal-
lation setup “
RH influence on Heating
” (s. 4.4). Refer to s. 10.1.2 for further information on this function.
RH Set Point:
Humidity level above which the com-
pensation using the heating outputs starts.
Adjustable from 20 to 99% of humidity.
Select “Off” to deactivate this function.
On Time:
Running times of the heating outputs
within the RH compensation heating cycles.
Adjustable from 15 to 300 seconds in
increments of 15 sec.
GRAPHIC:
Heaters’ timer
ON
ON TIME
OFF
CYCLE TIME
Main Menu
9.
Advanced Settings
10.
Select Program
Advanced Settings
3.
Relative Humidity Compensation
4.
Night Set Point Settings
RH Compensation Settings
Minimum Ventilation Compensation
RH Set Point
65 %
Add Speed
60 %
Stop RH Comp. Under 55.0 °F
Heater Compensation
RH Set Point
65 %
On Time
15 sec
Cycle Time
300 sec
Mist Shutoff at
85 %
Mist On Low % Relative Humidity
Low Setpoint
30 %
On Time
0:30 (m:s)
Off Time
2:00 (m:s)
Exit: Press Back
Change: Press Modify
Press to Select an Item