40
EXPERT 64EU rev.03
EXPERT 64EU
6.1.5 Minimum Ventilation Settings
Note that the minimum ventilation settings are common to all programs.
6.1.5.1
Main Options
Select
5. Minimum Ventilation
5. Options
• Set the following parameters.
(Refer to the previous section to get further information
on these parameters)
Use Variable 1-2 in Timer ?
Select “Yes” for the variable outputs to
operate following a timer during the mini-
mum ventilation cycles; select “No” for
variable outputs to operate continuously.
Refer to the following section to disable
variable fans in minimum ventilation.
Only available if variable outputs are enabled (sec. 4.5).
Use Fan Relay for Min. Vent ?
Select “Yes” to use On/Off fan relays in minimum ventilation.
Alternate Fan during On Time ?
Select “Yes” to alternate the fan selection during the minimum ventilation cycles.
Use Curve Settings ?
Select “Yes” to get an automatic adjustment of the minimum ventilation set-
tings over time. When enabled, the minimum ventilation parameters are set
separately for each point of the curve.
Change Fan Relays with Age ?
Select “Yes” if the bank of fan relays needs to be changed over time.
Main Menu
5.
Minimum Ventilation
6.
Inlet Setup
7.
Light Settings
8.
Start / Stop Temperature
9.
Advanced Settings
10.
Select Program
11.
Alarm Log
12.
Controller Setup
Submenu: Press Enter
Press
to Select an Item
Minimum Ventilation
4.
Fan Relay Assignment (10Steps)
5.
Options
Minimum Ventilation Options
Use Variable 1 in Timer ?
Yes
Use Variable 2 in Timer ?
Yes
Use Fan Relay for Min. Vent ? Yes
Alternate Fan during OnTime ? Yes
Use Curve Settings ?
Yes
Change Fan Relay with Age ?
Yes
Exit : Press Back Change: Press Modify
Press to Select an Item
Содержание Integra EXPERT 64EU
Страница 1: ...EXPERT 64EU Temperature Controller USER S MANUAL...
Страница 2: ......
Страница 100: ......
Страница 101: ......
Страница 102: ...M 890 00000 rev 03 REV 02...