6.3.2 Curtain Settings
Select
8. Start / Stop Temperature
4. Tunnel Curtain
• Set the appropriate parameters amongst the following:
(Refer to the previous section to get further information on these parameters)
Curtain starts opening at Fan Stage #x (1st Stage):
The tunnel curtain starts opening when the start temperature of this fan stage
is reached.
Curtain is fully opened at Stage #x:
(if the curtain is based on the temperature only)
The curtain fully opens when the start temperature of this fan stage is reached.
Minimum Age:
Animal age below which the tunnel ventilation mode is disabled. Adjustable
from 1 to 450 days. Select “Off” to disable this function.
Main Menu
8.
Start / Stop Temperature
9.
Advanced Settings
10.
Select Program
11.
Alarm Log
12.
Setup
Submenu: Press Enter
Press
to Select an Item
Start/Stop Temperature Settings
4.
Tunnel Curtain
5.
Clock Outputs
Tunnel Curtain Settings
1st Stage
3
100% open
4
Minimum age
10 days
Minimum outside temp.
50.0 °F
Tunnel Curtain Open Times
Stage 3
0:30 (m:s)
Stage 4
0:30 (m:s)
Stage 5
0:30 (m:s)
Stage 6
0:30 (m:s)
Stage 7
0:30 (m:s)
Exit: Press Back
Change: Press Modify
Press to Select an Item
Tunnel Curtain Settings
1st Stage
3
Minimum age
10 days
Minimum outside temp.
50.0 °F
Low Set Point
.04 WC
High Set Point
.06 WC
Summer Low Set Point
.04 WC
Summer High Set Point
.06 WC
Winter Low Set Point
.04 WC
Winter High Set Point
.06 WC
PreOpening
30 sec
Open Time
1:00 (m:s)
Close Time
1:00 (m:s)
Off Time
0:30 (m:s)
Exit: Press Back
Change: Press Modify
Press to Select an Item
or
Curtain – based on
the room T°
Curtain – based on
the static pressure