6.2.2.2
Setting the 0-10V Outputs (Used for Ventilation)
The following parameters are related to the 0-10V fan outputs that follow the same
progression of the regular fan stages. Refer to
section 4.5 to enable this function.
Select
8. Start / Stop Temperature
2. Fan Stages
• Set the appropriate parameters amongst
the following:
(Refer to the previous sections to get further informa-
tion on these parameters)
Start temperature:
This is the temperature at which the
0-10V output starts operating continu-
ously at its minimum speed. This tem-
perature is related to the main set point
which means that it is automatically
adjusted when the set point changes.
Adjustable from +/- 40°F (22.2°C)
from the set point.
Max Temperature:
This is the temperature at which the
output reaches its maximum speed. It
must be set to a greater value than the start temperature.
Fan Shutoff Temperature:
Temperature at which the 0-10V output is deactivated when the room tem-
perature increases. It must be set to a greater value than the start temperature.
Select “Off” to deactivate this function.
Min/Max Speeds:
Minimum and maximum speed of the 0-10V outputs. Adjustable from 0 to
100%. The maximum speed must be greater than the minimum speed.
On/Off times:
The 0-10V outputs operate following this timer when the room temperature is
below the start temperature. The timer’s On and Off times are adjustable from
0 to 900 seconds in increments of 15 seconds.
Main Menu
8.
Start / Stop Temperature
9.
Advanced Settings
Start / Stop Temperature Settings
1.
Heaters
2.
Fan Stages
3.
Coolings
4.
Tunnel Curtain 1
5.
Tunnel Curtain 2
6.
Clock Outputs
7.
0-10V Output 1
8.
0-10V Output 2
9.
0-10V Output 3
10.
0-10V Output 4
11.
Alarms
Exit: Press Back
Submenu: Press Enter
Press
to Select an Item
Fans Start/Stop Temperature
Fan Output 1 (0-10V)
Start Temperature
75.0 °F
Maximum Temperature
77.0 °F
Fan shutoff At
90.0 °F
Minimum Speed
10 %
Maximum Speed
100 %
On Time
15 sec
Off Time
0 sec
Fan 1 Start Temperature
70.0 °F
Summer
V1 Bandwidth
2.0 °F
V2 Bandwidth
2.0 °F
Winter
V1 Bandwidth
4.0 °F
V2 Bandwidth
4.0 °F
(...)
Fan 15 Start Temperature
70.5 °F
Stop Temperature
70.0 °F
On Time
0:15 (m:s)
Off Time 5:00 (m:s)
Press Back
Change: Press Modify
Press to Select an Item