21
EXPERT 64EU rev.03
EXPERT 64EU
• Outside Relative Humidity (RH) Probe:
Enable / disable the outdoor humidity probe input.
Common to all programs.
• Static Pressure (SP) Probe:
Enable / disable the static pressure probe input.
Common to all programs.
• Water Meter:
Enable / disable the water meter input.
Common to all programs.
• Temperature Units:
Select the temperature measuring units: Celsius (°C) /Fahrenheit (°F).
Common to all programs.
• Static Pressure Units:
Select the static pressure measuring units: inches of water ("WC) or Pascals (Pa).
Common to all programs.
• Water Meter Units:
Select the measuring units of the water level: liters (lit) or gallons (gal).
This parameter is only displayed if the water meter is enabled above. Common to all programs.
• Water meter’s calibration:
Adjust the water meter’s flow per pulse. Adjustable from 1 to 100 liters or
gallons per pulse.
This parameter is only displayed if the water meter is enabled above. Common to all programs.
• RH Influence on the Minimum Ventilation Speed:
Select “Yes” to enable this relative humidity compensation function.
Refer to sec. 10.1 for further information on this feature.
This parameter is only shown if the Room RH Probe is enabled above and if variable outputs are used (sec. 4.5).
• RH Influence on Heating Outputs:
Select “Yes” to enable this relative humidity compensation function.
Refer to sec. 10.1 for further information on this feature.
This parameter is only displayed if the Room RH Probe is enabled above.
• Mist Shutoff:
Select “Yes” to enable this relative humidity compensation function. Refer to
sec. 10.1 for further information on this feature.
This parameter is only displayed if the Room RH Probe is enabled above.
Содержание Integra EXPERT 64EU
Страница 1: ...EXPERT 64EU Temperature Controller USER S MANUAL...
Страница 2: ......
Страница 100: ......
Страница 101: ......
Страница 102: ...M 890 00000 rev 03 REV 02...