50
EXPERT 64EU rev.03
EXPERT 64EU
At the Maximum T°:
The output reaches its maximum capacity;
Above the "Fan Shutoff" temperature:
The output is deactivated.
6.2.2 Settings
6.2.2.1
Setting the Fan Stages
Select
8. Start / Stop Temperature
2. Fan Stages
• Set the appropriate parameters amongst
the following:
(Refer to the previous sections to get further informa-
tion on these parameters)
Start & Stop Temperatures:
Set the start and stop temperatures of
each fan stage. Note that the minimum
temperature difference between two
consecutive start temperatures is 0.5°F
(0.3°C).
Bandwidths:
Set the number of degrees that is re-
quired for the variable outputs to reach
their full speed within the ventilation
stages (s. 6.2.1.2). Set the bandwidths
separately for winter and for summer if the outside temperature compensation
is enabled. The bandwidths can be adjusted from 0.5 to 20.0°F (0.3 to 11.1°C).
Timer:
Set the On and Off times of each fan stage that activates a timer relay
(s. 6.2.1.1). The On and Off times can be adjusted from 0 to 99 minutes in
increments of 15 seconds.
Main Menu
8.
Start / Stop Temperature
9.
Advanced Settings
10.
Select Program
11.
Alarm Log
12.
Controller Setup
Submenu: Press Enter
Press
to Select an Item
Start / Stop Temperature Settings
1.
Heaters
2.
Fan Stages
3.
Coolings
4.
Tunnel Curtain 1
5.
Tunnel Curtain 2
6.
Clock Outputs
7.
0-10V Output 1
8.
0-10V Output 2
9.
0-10V Output 3
10.
0-10V Output 4
11.
Alarms
Exit: Press Back
Submenu: Press Enter
Press
to Select an Item
Fans Start/Stop Temperature
Fan Output 1 (0-10V)
Start Temperature
75.0 °F
Maximum Temperature
77.0 °F
Fan shutoff At
90.0 °F
Minimum Speed
10 %
Maximum Speed
100 %
On Time
15 sec
Off Time
0 sec
Fan 1 Start Temperature
70.0 °F
Summer
V1 Bandwidth
2.0 °F
V2 Bandwidth
2.0 °F
Winter
V1 Bandwidth
4.0 °F
V2 Bandwidth
4.0 °F
(...)
Fan 15 Start Temperature
70.5 °F
Stop Temperature
70.0 °F
On Time
0:15 (m:s)
Off Time 5:00 (m:s)
Press Back
Change: Press Modify
Press to Select an Item
Содержание Integra EXPERT 64EU
Страница 1: ...EXPERT 64EU Temperature Controller USER S MANUAL...
Страница 2: ......
Страница 100: ......
Страница 101: ......
Страница 102: ...M 890 00000 rev 03 REV 02...