73
EXPERT 64EU rev.03
EXPERT 64EU
10.1.3 RH Compensation with Cooling Outputs
Compensation for a high
humidity level (Mist Shutoff):
If the humidity level is too
high, the mist units (cooling
outputs and the fan stages’
timer relays) can be shut off
to avoid increasing the humid-
ity level any further. The cool-
ing outputs are stopped
whenever the humidity level
increases above the mist
shutoff limit.
Compensation for a low
humidity level:
The mist cooling outputs are
activated according to a timer
whenever the humidity level
decreases below the
Low RH
Set Point.
GRAPHIC:
Mist Shutoff on high humidity levels
MIST SHUTOFF
RELATIVE HUMIDITY
LEVEL (%)
COOLING
OUTPUT
THE COOLING
OUTPUT STOPS
OPERATING
GRAPHIC:
Mist activation on low humidity levels
LOW RH
SET POINT
RELATIVE HUMIDITY
LEVEL (%)
COOLING
OUTPUT
THE COOLING
OUTPUT OPERATES
ACCORDING
TO A TIMER
Содержание Integra EXPERT 64EU
Страница 1: ...EXPERT 64EU Temperature Controller USER S MANUAL...
Страница 2: ......
Страница 100: ......
Страница 101: ......
Страница 102: ...M 890 00000 rev 03 REV 02...