20
EXPERT 64EU rev.03
EXPERT 64EU
4.4
Installation Setup
The following section shows how to customize the controller for your particular
application. It shows how to enable the controller’s inputs, to select the desired
measuring units and to set other basic functions of your controller. Normally, this
setup needs to be done only once for each program.
Pay attention. Some of the Installation Setup parameters are common to all
programs. Templates are available at the end of this manual to write down
the specific settings of each program.
Select
12. Controller Setup
1. Installation*
* Only accessible from the installer mode (s. 4.2).
• Set the appropriate parameters
amongst the following:
• Number of Programs:
Select the number of controller pro-
grams. Ranges from 1 to 3 programs.
Common to all programs.
• Time Display:
Select AM/PM or 24 hours.
Common to all programs.
• # of Temperature Probes:
Select the number of indoor
temperature probes connected to the
controller, excluding the outside tem-
perature probe. Adjustable from 1 to 8
probes.
Common to all programs.
• Outside temperature probe:
Enable / disable the outside T° probe input.
Common to all programs.
• Room Relative Humidity (RH) Probe:
Enable / disable the room humidity probe input.
Common to all programs.
Main Menu
11.
Alarm Log
12.
Controller Setup
Controller Setup
1.
Installation
2.
Output Setup
3.
Copy / Paste Program
4.
Password
5.
Relay Assignment
6.
Variable Output Assignment
7.
Probe Assignment
8.
Version
9.
Test Mode
Submenu: Press Enter
Press to Select an Item
Installation
Number of Programs
3
Time of day format
AM/PM
Number of T° Probes
8
Use Outside T° Probe?
Yes
Use Room RH Probe?
Yes
Use Outside RH Probe?
Yes
Use Static Pressure?
Yes
Use Water Meter?
Yes
Temperature Units
°F
Static Pressure Units
WC
Water Meter Units
gal
Water Meter Calibration
1 gal/p
RH influence on min vent?
Yes
RH influence on Heating?
Yes
Use Mist Shutoff?
Yes
Use Mist on Low R.Humidity
Yes
Out T influence bandwidth
Yes
Summer Temperature
59.0°F
Winter Temperature
41.0°F
Use Night Set Point?
No
Show on Digit Display
T°