POSSIBLE RESULTS
CONNECTING AN EXTERNAL FLOW METER
Most metered commercial units require an external flow meter device. this requires an entry in the programming
for the meter chosen. The entry is the pulses per gallon, or K Factor. Refer to the table on the page 63 for meter K
Factors.
From the home screen, press the
DOWN
arrow to
ACCESSORIES
. Press the
CHECK
MARK
button.
Press the
DOWN
arrow key to scroll to
FLOW
METER
and press the
CHECK
MARK
button.
To change the value, press the
CHECK
MARK
button and then use the UP
ARROW
or
DOWN
ARROW
keys. Press the
CHECK
MARK
button when done. Note: Hi-Flo 22 is
to be set at 78 puls/Gal.
Press the
X
key until you return to the main screen.
SETTING UP A MULTI-TANK SYSTEM
A Multi-tank system requires additional programming.
REMINDER:
Any additional program changes such as REGEN SETUP, CYCLE TIMES and REGEN TRIGGER must
be programmed into each control in the system.
From the home screen, press the
DOWN
arrow to
ACCESSORIES
. Press the
CHECK
MARK
button.
Press the
DOWN
arrow key to scroll to
SYSTEM SETUP
and press the
CHECK MARK
button.
> 4) Accessories
> 9) Flow Meter
Flow Meter
80.0 Puls/Gal
modem email
success
modem test time
set success
modem test
checking for new fw
modem test
no new fw
Installation of Accessories
system ok
7:32 am 2-1-08
> 5) adv setup
> 1) system setup
Installation of Accessories
42
41
CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Содержание GBE
Страница 62: ...Menu Overview Continued on page 61 59 CULLIGAN GLOBAL ELECTRONIC CONTROLLER ...
Страница 63: ...Menu Overview Menu Overview 60 ...
Страница 64: ...Menu Overview Continued from page 59 61 CULLIGAN GLOBAL ELECTRONIC CONTROLLER ...
Страница 65: ...Menu Overview Menu Overview 62 ...
Страница 72: ...Appendix D 69 CULLIGAN GLOBAL ELECTRONIC CONTROLLER ...