Cycle Times
•
Press the
UP
„
or
DOWN
‰
arrow to scroll to menu item
•
Press the
CHECKMARK
P
key to select a menu item
• Press the
UP
„
or
DOWN
‰
arrow to change a selection
•
Press the
CHECKMARK
P
key to save your selection
Default Values are shown for each selection
Scroll to ADV SETUP and select
Select CYCLE TIMES
Select either USE DEFAULTS or CUSTOM. When USE DEFAULTS is selected, the pro-
gram calculates the cycle times based on hardness and resin volume. When CUSTOM is
selected, you can set custom cycle times.
Use this setting to adjust the number of minutes for backwash. You generally will not
need to change this setting.
For commercial applications, this value can normally be set to 60 minutes. It can be
extended if you find the brine is not being rinsed out properly within this time.
This value is calculated for household units. For commercial units, you should adjust this
value to 10 minutes, but it is not required.
This will only show if you have selected a 5-cycle valve. This is the refill time. This value
can be found in the unit’s installation manual. For example, if you have a Hi-Flo 22 WS-
90 water softener (3 ft³) and you want to set a capacity of 60,000 grains, then using
the chart in Appendix A of the Hi-Flo 22 manual show a time setting of 12 minutes.
For a 4-cycle valve, the refill is controlled by AUX OUTPUT 2 and the refill time is set
there. See page 46.
This concludes the Cycle Times section. Continue to press the
X
key to return to the Main Menu.
> 5) Adv Setup
system ok
7:32 am 2-1-08
> 3) cycle times
cycle times
>use defaults
backwash time
10 minutes
brine draw-rinse
71 minutes
fast rinse
7 minutes
Customizing the Setup
Customizing the Setup
32
31
CULLIGAN GLOBAL ELECTRONIC CONTROLLER
fill Time
7 minutes
Содержание GBE
Страница 62: ...Menu Overview Continued on page 61 59 CULLIGAN GLOBAL ELECTRONIC CONTROLLER ...
Страница 63: ...Menu Overview Menu Overview 60 ...
Страница 64: ...Menu Overview Continued from page 59 61 CULLIGAN GLOBAL ELECTRONIC CONTROLLER ...
Страница 65: ...Menu Overview Menu Overview 62 ...
Страница 72: ...Appendix D 69 CULLIGAN GLOBAL ELECTRONIC CONTROLLER ...