34
V. Condensate Disposal
(continued)
Figure 18: Condensate Trap and Drain Line
2. Limestone chips in neutralizers will get coated
by salts (product of chemical reaction between
limestone and acidic condensate) and lose
neutralizing effectiveness over time. Therefore,
periodic condensate neutralizer maintenance and
limestone chip replacement must be performed. A
pH test or acid test kits are available from HVAC/
plumbing distributors and should be used to measure
condensate acidity before/after neutralizer thus
indicating a need for service and chip replacement.