25
IV. Venting
C. Polypropylene Venting
Boiler
Model
M&G / DuraVent Part Numbers/Sizes
Male Boiler Adapter,
PVC to PP
Rigid Pipe
Nominal Dia.
Flex Pipe
Nominal Dia.
Pipe Joint
Locking Band
Side Wall
Termination Tee
Chimney Kit for
Venting Only
PHNTM399
4PPS-04PVCM-4PPF
4 in.
(100 mm)
4 in.
(100 mm)
43PPS-LB
43PPS-TB
4PPS-FK
PHNTM500
Table 10A: Listed Polypropylene Pipe, Fittings and Terminations - M&G/DuraVent
Boiler
Model
Centrotherm Eco Part Numbers/Sizes
Male Boiler Adapter,
PVC to PP
Rigid Pipe
Nominal Dia.
Flex Pipe
Nominal Dia.
Pipe Joint
Locking Band
Side Wall
Termination Tee
Chimney Kit for
Venting Only
PHNTM399
ISAA0404
ISSAL0404
4 in.
(110 mm)
4 in.
(110 mm)
IANS04
ISTT0420
IFCK0425
and
IFCK0435
PHNTM500
Table 10B: Listed Polypropylene Pipe, Fittings and Terminations - Centrotherm Eco
Systems’.
ii.
Centrotherm Eco Systems InnoFlue SW
Rigid Vent and Flex Flexible Vent comply
with the requirements of UL 1738 ‘Standard
for Safety for Venting Systems’ and
ULC-S636-08 ‘Standard for Type BH Gas
Venting Systems’.
b. See Table 10A for specific M&G Duravent
System Connector” under “B. CPVC/PVC
Venting.” See Figures 9 and 14.
b. Apply provided dielectric grease (grease pouch
taped to the vent system connector) all around
to the vent or air connection inner red silicon
gasket.
c. Push and twist PVC to PP adapter into two-pipe
vent system connector vent or combustion air
supply port until bottomed out.
d. Tighten the worm band clamp screw to secure
PVC to PP adapter.
e. Do not install PVC to PP adapter at the lower
combustion air supply port of the two-pipe vent
system connector when using PVC pipe for
combustion air supply to boiler.
3. System Assembly
a. Plan venting system to avoid possible contact
with plumbing or electrical wires. Start at
vent connector at boiler and work towards vent
termination.
b. Follow all manufacturer instructions and
warnings when preparing pipe ends for joining
and when assembling the vent/combustion air
system.
c. Use locking band clamps at all vent pipe joints.
Figure 14: Vent System Field Modification to Install
PVC to PP Adapter (M&G/DuraVent Shown)
components.
c. See Table 10B for specific Centrotherm Eco
Systems components.
2. Field Installation of CPVC/PVC Two-
Pipe Vent System Connector and PVC to
Polypropylene Adapter
a. Install CPVC/PVC two-pipe vent system
connector. Follow instructions in “2. Field
Installation of CPVC/PVC Two-Pipe Vent
Содержание PHNTM399
Страница 6: ...6 I Product Description Specifications and Dimensional Data continued Figure 1A Phantom Model PHNTM399...
Страница 7: ...7 Figure 1B Phantom Model PHNTM500 I Product Description Specifications and Dimensional Data continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Ladder Diagram...
Страница 54: ...54 VIII Electrical continued...
Страница 55: ...55 Figure 27 Wiring Connections Diagram VIII Electrical continued...
Страница 63: ...63 IX System Start up continued Phantom Series Operating Instructions Figure 32 Operating Instructions...
Страница 113: ...113 THIS PAGE LEFT BLANK INTENTIONALLY...
Страница 114: ...114 XIII Repair Parts continued PHNTM399 and PHNTM500...
Страница 118: ...118...
Страница 119: ...119...