IV. Venting
D. Stainless Steel Venting
Figure 16: Field Installation of Two-Pipe Vent
System Adapter for Stainless Steel
D. Stainless Steel Venting
WARNING
Asphyxiation Hazard. Follow these instructions
and the installation instructions included by
the original stainless steel venting component
manufacturers, Heat Fab, M&G/DuraVent or
Z-Flex, whichever applicable. Failure to do
so could cause products of combustion to
enter the building, resulting in severe property
damage, personal injury or death. Where
a conflict arises between Heat Fab, M&G/
DuraVent or Z-Flex instructions and these
instructions, the more restrictive instructions
shall govern.
Do not mix vent components from listed
manufacturers.
Examine all components for possible
shipping damage prior to installation.
All condensate that forms in the vent must
be able to drain back to the boiler.
NOTICE
Do not exceed maximum vent/combustion
air system length. Refer to “2. Vent/
Combustion Air Piping” under “A. General
Guidelines” in this section for maximum
vent/combustion air system length.
Use only vent and combustion air terminals
and terminal locations shown in “3. Vent/
Combustion Air Terminals” under “A.
General Guidelines” of this section.
1. Components
a. Acceptable listed stainless steel vent system
manufacturers and components are shown in
Table 11.
b. Where the use of “silicone” is called for in the
following instructions, use GE RTV 106 or
equivalent for the vent collar. Seal galvanized
combustion air piping sections with any general-
purpose silicone sealant such as GE RTV102.
Seal PVC combustion air piping sections with
PVC cement.
c. Do not drill holes in vent pipe.
2. Field Installation of CPVC/PVC Two-Pipe
Vent System Connector and PVC to Stainless
Steel Adapter
a. Install CPVC/PVC two-pipe vent system
connector. Follow instructions in “2. Field
Installation of CPVC/PVC Two-Pipe Vent
System Connector” under “B. CPVC/PVC
Venting.” See also Figures 9 and 16.
b. Apply provided dielectric grease (grease pouch
taped to the vent system connector) all around
to the vent or air connection inner red silicon
gasket.
c. Push and twist PVC to stainless steel adapter
into two-pipe vent system connector vent or
combustion air supply port until bottomed out.
See Figure 16.
d. Tighten the worm band clamp screw to secure
PVC to stainless steel adapter.
e. Do not install PVC to stainless steel adapter
at the lower combustion air supply port of the
two-pipe vent system connector when using PVC
pipe for combustion air supply to boiler.
3. System Assembly
WARNING
Asphyxiation Hazard. Vent systems made
by Heat Fab, M&G / DuraVent and Z-Flex rely
on gaskets for proper sealing. When these
vent systems are used, take the following
precautions:
• Make sure that gasket is in position and
undamaged in the female end of the pipe.
• Make sure that both the male and female
pipes are free of damage prior to assembly.
• Only cut vent pipe as permitted by the
vent manufacturer in accordance with their
Instructions. When pipe is cut, cut end must
be square and carefully de-burred prior to
assembly.
a. Plan venting system to avoid possible contact
with plumbing or electrical wires. Start at
vent connector at boiler and work towards vent
termination.
b. Follow all manufacturer instructions and
warnings when preparing pipe ends for joining
and when assembling the vent/combustion air
system.
Содержание PHNTM399
Страница 6: ...6 I Product Description Specifications and Dimensional Data continued Figure 1A Phantom Model PHNTM399...
Страница 7: ...7 Figure 1B Phantom Model PHNTM500 I Product Description Specifications and Dimensional Data continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Ladder Diagram...
Страница 54: ...54 VIII Electrical continued...
Страница 55: ...55 Figure 27 Wiring Connections Diagram VIII Electrical continued...
Страница 63: ...63 IX System Start up continued Phantom Series Operating Instructions Figure 32 Operating Instructions...
Страница 113: ...113 THIS PAGE LEFT BLANK INTENTIONALLY...
Страница 114: ...114 XIII Repair Parts continued PHNTM399 and PHNTM500...
Страница 118: ...118...
Страница 119: ...119...