IX. System Start-up
(continued)
WARNING
Asphyxiation Hazard. If the throttle is very far out of adjustment on the “rich” (counter-clockwise) side,
the boiler burner may be running at 0% excess air or even with air deficiency. Operating the boiler in this
condition may cause property damage, personal injury or loss of life.
Under these conditions most combustion analyzers used in the field will show 0% O
2
and a very high (well
over 1000 ppm) CO. Combustion readings will also appear to be unresponsive to throttle adjustment.
If the boiler appears to operate under these conditions, shut down the boiler and follow instructions in
Paragraph S “Correcting Throttle Screws Mis-Adjustment. Then, use a combustion analyzer to verify and
adjust O
2
(or CO
2
) and CO to values shown in Table 22 for natural gas or Table 23 for LP gas.
Содержание PHNTM399
Страница 6: ...6 I Product Description Specifications and Dimensional Data continued Figure 1A Phantom Model PHNTM399...
Страница 7: ...7 Figure 1B Phantom Model PHNTM500 I Product Description Specifications and Dimensional Data continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Ladder Diagram...
Страница 54: ...54 VIII Electrical continued...
Страница 55: ...55 Figure 27 Wiring Connections Diagram VIII Electrical continued...
Страница 63: ...63 IX System Start up continued Phantom Series Operating Instructions Figure 32 Operating Instructions...
Страница 113: ...113 THIS PAGE LEFT BLANK INTENTIONALLY...
Страница 114: ...114 XIII Repair Parts continued PHNTM399 and PHNTM500...
Страница 118: ...118...
Страница 119: ...119...