47
VII. Gas Piping
WARNING
Explosion Hazard. Failure to properly pipe gas
supply to boiler may result in improper operation
and damage to the boiler or structure. Always
assure gas piping is absolutely leak free and of
the proper size and type for the connected load.
An additional gas pressure regulator may be
needed. Consult gas supplier.
NOTICE
Size corrugated stainless steel tubing (CSST)
to ensure proper capacity and minimize flow
restrictions.
A. Size gas piping. Design system to provide
adequate gas supply to boiler. Consider
these factors:
Inlet Pressure 13.8 in wc (3.4 kPa)or less; 0.3 in wc (0.07 kPa) Pressure Drop
Nominal Pipe
Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
131
90
72
62
55
50
46
42
40
38
¾
0.824
273
188
151
129
114
104
95
89
83
79
1
1.049
514
353
284
243
215
195
179
167
157
148
1¼
1.380
1056
726
583
499
442
400
368
343
322
304
1½
1.610
1582
1087
873
747
662
600
552
514
482
455
2
2.067
3046
2094
1681
1439
1275
1156
1063
989
928
877
2½
2.469
4856
3337
2680
2294
2033
1842
1695
1576
1479
1397
3
3.068
8584
5900
4738
4055
3594
3256
2996
2787
2615
2470
Table 17A: Maximum Capacity of Schedule 40 Black Pipe in CFH* (Natural Gas) For Gas Pressures
of 1/2 psi (3.4 kPa) or Less
Inlet Pressure 13.8 in wc (3.4 kPa) or less; 0.5 in wc (0.12 kPa) Pressure Drop
Nominal Pipe
Size, In.
Inside
Diameter, In.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
172
118
95
81
72
65
60
56
52
50
¾
0.824
360
247
199
170
151
137
126
117
110
104
1
1.049
678
466
374
320
284
257
237
220
207
195
1¼
1.380
1392
957
768
657
583
528
486
452
424
400
1½
1.610
2085
1433
1151
985
873
791
728
677
635
600
2
2.067
4016
2760
2217
1897
1681
1523
1402
1304
1223
1156
2½
2.469
6401
4400
3533
3024
2680
2428
2234
2078
1950
1842
3
3.068
11316
7778
6246
5345
4738
4293
3949
3674
3447
3256
* 1 CFH of Natural Gas is approximately equal to 1 MBH; contact your gas supplier for the actual heating value of your
gas.
1. Allowable pressure drop from point of
delivery to boiler.
Maximum allowable system
pressure is ½ psig (3.4 kPa). Actual point of delivery
pressure may be less; contact gas supplier for
additional information. Minimum gas valve inlet
pressure is printed on the rating label located in the
boiler’s vestibule compartment.
2. Maximum gas demand.
Refer to the boiler’s
input as printed on its rating label. Also consider
existing and expected future gas utilization
equipment (i.e. water heater, cooking equipment).
3. Length of piping and number of fittings.
Refer to Tables 16A (natural gas) or 16B (LP gas)
for maximum capacity of Schedule 40 pipe. Table
18 lists equivalent pipe length for standard fittings.
4. Specific gravity of gas.
Gas piping systems for
gas with a specific gravity of 0.60 can be sized
directly from Table 17A and gas with a specific
gravity of 1.5 can be sized from Table 17B, unless
authority having jurisdiction specifies a gravity
factor be applied. For other specific gravity, apply
gravity factor from Table 19. If exact specific
gravity is not shown choose next higher value.
Содержание PHNTM399
Страница 6: ...6 I Product Description Specifications and Dimensional Data continued Figure 1A Phantom Model PHNTM399...
Страница 7: ...7 Figure 1B Phantom Model PHNTM500 I Product Description Specifications and Dimensional Data continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Ladder Diagram...
Страница 54: ...54 VIII Electrical continued...
Страница 55: ...55 Figure 27 Wiring Connections Diagram VIII Electrical continued...
Страница 63: ...63 IX System Start up continued Phantom Series Operating Instructions Figure 32 Operating Instructions...
Страница 113: ...113 THIS PAGE LEFT BLANK INTENTIONALLY...
Страница 114: ...114 XIII Repair Parts continued PHNTM399 and PHNTM500...
Страница 118: ...118...
Страница 119: ...119...