CEAG Notlichtsysteme GmbH
63
Operating
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Menu 6
Add / remove
Luminaire search
Text assignments
DLS/TLS-Assignment
Selection of
menu options
with the keys
<ok>:
confirm selec-
tion
<Menu>: cancel
and return to
the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Line selection (line 2 and 3) with
Select a luminaire in line 2 with keys
(line 4 shows “not installed” or the
luminaire name)
possible selections in line 3 with keys
(see table below)
If there are two switch assignments
in line 3, use keys
to toggle be-
tween these displays.
Finish and return to Menu 6 with
<Menu>
<ok>
Menu 6.4:
Module8
circuit:2
...5.....10.....15....2
s.Stromkreis DLS/TLS
Circuit name
Select the input fields in line 1 with
Select input field with
The displays and input options depend
on the technical characteristics of the
luminaires that are used and on the
settings made in menu 5 “Circuit set-
up”
A switch cannot be assigned to individual luminaires unless the options “CG monitor-
ing” (compare menu 5.4) and “per luminaire setup” (compare menu 5.5) are selected;
the following display appears:
Add / remove
Luminaire search
Text assignments
DLS/TLS-Assignment
Table of selection options in line 3 for an installed CG-S luminaire
“no CG-S function”
The luminaire is not individually monitored and not
switchable
“Non-maintained mode” The CG-S luminaire is individually monitored and
is off in normal operation
“Maintained light”
The CG-S luminaire is individually monitored and
is on in normal operation
“Poll1 / Poll2”
The CG-S luminaire is individually monitored and
it is assigned a certain switch configuration.
It can be assigned 2 switches:
“DLS xx/y
DLS xx/y
(OR operation)
It can be assigned 1 timer and a switch:
“Timer 1
DLS xx/y
”
“Timer 2
DLS xx/y
”
“Timer 1 & 2
DLS xx/y
”
xx: Module number ( 1 to 10) y: Inputs of the module (e.g. for switch interrogation)
Module8
circuit:2
....5...10...15...20
Line 3
Luminaire text