Operating
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
<ok>
Menu 1.1: Request in view of the of station
to be tested (M3-Mode, compare note M3)
<ok> initiates a function test for the
connected final circuits:
The graphic display shows the main
screen with the message “Function test”.
The function of the connected luminaires is
queried and shown on the display following
the function test lead time of 0 s to 900
s, settable in the basic settings/function
test menu.
Further information can be polled in the
following submenus of the Test & Status
Menu (e.g. “1.2 Sum failure info” etc.).
Start functiontest
Sum failure info
Circuit state
Luminaire state
etc.
Select input field with
Select installed modules or the circuits
set up under circuit setup with
Finish and return to Menu 3 with
<Menu> or <ESC>
Line 3: Displays the additional informa-
tion, e.g. «Waiting for module data» or
«FT-Current value 1,2A»
<ok>
Menu
1.3:
Line 2: Possible status displays:
Circuit blocked
Emergency operation
Normal operation
Function test pre-run
Function test
Module 2/1
circuit:1
Status display
Add. information
Circuit name
Note M3
In the Multi-Master-Mode this
operation can be effected at any
station of the system:
Device address referes to search
results in the substation setup
menu 3 «Basic settings»
this device
all devices
Device address 01
Device name
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Menu 1
Start functiontest
Sum failure info
Circuit state
Luminaire state
DLS/TLS/3PhW state
Relay state
Selection of
menu options
with the keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes
entered are
saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
8.4.1 Menu 1: “Test & Status Menu”
<ok>
Menu 1.4:
Module 2/1
circuit:1
....5.....10.....15....2
—-
————————
-
Circuit name
Select input field/line with
Select module or circuit with
Line 3 shows the current settings of
the luminaire addresses (1 ... 20) in the
selected circuit:
Luminaire is off (Item 1)
Luminaire is on (Item 2)
Luminaire failure (Item 3)
– no luminaire set up (Item 4)
(see “6 Luminaire Setup”)
Select a luminaire (line 2) with
Line 4 shows the luminaire name
(see “6.3 Text assignments”)
<ok>
Menu 1.2: Displays the list of fault mes-
sages.
Start functiontest
Sum failure info
Circuit state
Luminaire state
etc.
Start functiontest
Sum failure info
Circuit state
Luminaire state
etc.
Start functiontest
Sum failure info
Circuit state
Luminaire state
etc.
Successive polling with
If a number of fault messages have accu-
mulated, they can be viewed in succes-
sion on the graphic display.
Sum failure
List: Failure 1
Failure 2
Failure 3
etc.