CEAG Notlichtsysteme GmbH
71
Appendix
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
Note:
Comply with the national regulations and guidelines for indicating and signalling when using a remote switch or
remote indicator for emergency lighting systems.
Contact assignment:
C0/14: NO C0/24: NO C0/34: NO C1/44: NO
C0/12: NC C0/22: NC C0/32: NC C1/54: NO
Note:
NO = normally open
NC = normally closed
The device has 5 floating signalling contacts (relay outputs) and one buzzer inside the device.
Signal contacts K3, K4, K5 can be freely parameterised, for each: 1 x changeover contact with common potential
1 x 24V; 0.5A
Relay contacts K1 (function test on), K2 (technical switching cabinet ventilation) with fixed assignment, each: 1 x make
contact with common potential 1 x 24V; 0.5A.