CEAG Notlichtsysteme GmbH
55
Operating
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
Buzzer setup
Ready
Mains failure S3/S4
Mains failure DLS/3PH
Ext. source error
Circuit fault
Luminaire fault
Device fault
Ext. source active
ISO error
Function test
Invert contact
Load defaults
<ok>
Menu 3.8:
Select the system or fault messages which
activate the buzzer in the switch cabinet.
A standard setting according to DIN VDE
(see Appendix B) can be selected using
the “Load defaults” option at the end of
this menu.
Highlight the events with
Select buzzer “On” (
) or buzzer
“
O
FF
”
(no
) with keys
Finish and return to Menu 3 with
<Menu>
Note:
The buzzer’s maintained signal tone
(after the onset of an event specified
here) can be silenced by pressing
any key.
Note:
“Brightness (on)” is the display setting when the display is active (press any key to
activate). If no key is pressed within 180 seconds, the controller switches the display
to passive (dimmed backlighting) “Brightness (off)”.
The above settings may make the display unreadable (e.g. depending on the ambient
lighting).
(The active display setting can be changed at any time from the main screen by pressing
<ok> and a key (for contrast) or (for brightness) of the active graphic display.)
Setting contrast and brightness (back-
lighting) for the graphic display of the
CU S
+
control module.
Line selection (2 to 4) with
Set the values (0 to 100%) with keys
Finish and return to Menu 3 with
<Menu>
<ok>
Menu 3.9:
Display setting
Contrast 50%
Brightness on:100%
Brightness off: 10%
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
etc.
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
etc.
Relay setup
Buzzer setup
Display setup
Timer setup
etc.
<ok>
Menu 3.10:
Timer deactivated/activated
00:00 - 23:59
Mo Tu We Th Fr Sa Su
X X X X X X X
Selection of Timer 1, Timer 2 or
Timer 1&2 with the buttons
If there appeares a X under the token
of the weekday, on this day the lumi-
naire operates to programmed time.
Overview:
Main menu
Test & status menu
Block,reset
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Memory card
Menu 3
Language
Date & time
Functiontest
Delay time mains return
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
Timer setup
Substation setup
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
Password protection
Daylight saving time
Service info
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes
entered are
saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Содержание Ceag AT-S+ C0