Operating
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
This option can be used to assign func-
tions to the option inputs (Z1 ... Z4 on the
control module); the functions are executed
as soon as the relevant 24V analog inputs
are triggered.
Only one function can be assigned per
input; the star icon goes out when an input
is assigned another function.
Select the option input
(1 to 4) with keys
Highlight the events with
Select the function (
) with <ok>
Finish and return to Menu 3 with
<Menu>
Substation setup
Connection to BMS
Function keys
Optional inputs
etc.
<ok>
Menu 3.14:
1
)
2
)
Option input 1
No function
Switch
Switch inverted
Manual reset
Start functiontest
all luminaires on
F-Test cancellation
Block device
maintained off
non-maintained on
Ventilator monitor
Ext. ISO monitor
Ext. Battery monitor
Ext. Monitor
Ext. Source ready
Ext. Source active
Ext. Source failure
Notes:
1
) The “Switch” assignment allows integration into the switch assignment (see menu options 5.4 and
6.3 “Switch assignments” in menus 5 “Circuit setup” and 6 “Luminaire setup”.
2
) The “Switch inverted” assignment initiates the function when the analog inputs are triggered inverted.
Important note!
The “Switch”, “Switch inverted”, “all luminaires on”, “Ventilator monitor”, “Ext. ISO monitor”,
“Ext. Battery Monitor”, “Ext. Monitor”, “Ext. Source ready”, “Ext. Source active”, “Ext. Source
failure functions” require a 24 V level trigger. All other functions require an edge-triggered signal
from LOW to HIGH.
<ok>
Menu 3.15:
Type: AT-S+
Serial No:123456/02
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
etc.
Overview:
Main menu
Test & status menu
Block,reset
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Memory card
Menu 3
Language
Date & time
Functiontest
Delay time mains return
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
Timer setup
Substation setup
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
Password protection
Daylight saving time
Service info
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes
entered are
saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
Содержание Ceag AT-S+ C0